Název: Optimized protection coordination of microgrids considering power quality-based voltage indices incorporating optimal sizing and placement of fault current limiters
Autoři: Azimi, Abolfazl
Hashemi Dezaki, Hamed
Citace zdrojového dokumentu: AZIMI, A. HASHEMI DEZAKI, H. Optimized protection coordination of microgrids considering power quality-based voltage indices incorporating optimal sizing and placement of fault current limiters. Sustainable Cities and Society, 2023, roč. 96, č. September 2023, s. nestránkováno. ISSN: 2210-6707
Datum vydání: 2023
Nakladatel: Elsevier
Typ dokumentu: článek
article
URI: 2-s2.0-85159369599
http://hdl.handle.net/11025/52995
ISSN: 2210-6707
Klíčová slova v dalším jazyce: optimal placement and sizing of fault current;limiters (FCLs);power quality voltage-based objective;voltage sag energy index (VSEI);optimal protection coordination;directional overcurrent relays (DOCRs);microgrids (MGs)
Abstrakt v dalším jazyce: Several solutions, such as fault current limiters (FCLs), have been utilized to mitigate the challenges of smart grids and ADNs’ protection schemes. However, less attention has been paid to simultaneously optimizing the protection coordination and power quality (PQ) concerns, incorporating the FCLs. There is a research gap in the literature in developing a method for optimal placement and impedance value of FCLs to optimize the speed of the protection systems, voltage sag energy index, and voltage sag duration. This research aims to fill such a research gap by proposing a new multi-objective optimization problem based on the optimum placement and impedance value of FCL. The proposed method is examined by implementing the distribution network of the IEEE 30-bus test system. MATLAB and DIgSILENT are linked online to simulate the protection of the smart grid and PQ voltage-based analyses and find the best solutions by the genetic algorithm (GA). The comparative analyses infer that a 13.13% improvement in criteria, e.g., operating time of relays, voltage sag energy, and voltage sag duration, is achieved by optimal placement of FCLs, beside other decision variables.
Práva: Plný text je přístupný v rámci univerzity přihlášeným uživatelům
© Elsevier B.V.
Vyskytuje se v kolekcích:Články / Articles (RICE)
OBD

Soubory připojené k záznamu:
Soubor VelikostFormát 
Dezaki_1-s2.0-S2210670723002457-main.pdf5,32 MBAdobe PDFZobrazit/otevřít  Vyžádat kopii


Použijte tento identifikátor k citaci nebo jako odkaz na tento záznam: http://hdl.handle.net/11025/52995

Všechny záznamy v DSpace jsou chráněny autorskými právy, všechna práva vyhrazena.

hledání
navigace
  1. DSpace at University of West Bohemia
  2. Publikační činnost / Publications
  3. OBD